PG25 Coolant: Property Table, OCP Limits and CDU Derates
A property table from −5 to 60 °C, the OCP PG25 guideline limits (Revision 2.0, September 2026), and what substituting PG25 for water costs in flow, pump power and heat transfer — with the capacity derate those costs force on a CDU. Free download: PG25 loop commissioning and fluid-care checklist (PDF).

What Is PG25?
PG25 is an inhibited mixture of about 25 % propylene glycol and 75 % water (inhibitors included in the water share), used as the coolant of the secondary loop — the technology cooling system (TCS) between the cooling distribution unit (CDU) and the cold plates — in direct-to-chip liquid cooling. The glycol gives freeze and burst protection and keeps the fluid biostatic; the inhibitor package protects the mixed-metal loop (copper cold plates, stainless piping). The Open Compute Project defines the percentage by volume: a new PG25 fill should be 24.5–27.5 vol % glycol, and an in-service fluid is kept within 24–29 %.
- −13 to −10 °Cfreeze point of new PG25 (9–14 °F), OCP, by ASTM D3321
- 1,024 kg/m³density at 20 °C (1,015 at 40 °C)
- 3.91 kJ/(kg·K)specific heat at 20 °C, about 94 % of water
- 2.47 mPa·sviscosity at 20 °C, about 2.5× water
- 17–66 °Ctypical TCS operating range named by OCP
- ConductiveOCP’s example in-line range is 1,000–10,000 µS/cm
Property values: generic correlation, table below. Limits and ranges: OCP Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0 (15 September 2026), pages 14–15, 25, 67 and 82.
PG25 Properties Table: Density, Specific Heat, Viscosity, Thermal Conductivity
The OCP guideline sets chemistry limits but publishes no thermophysical properties, and most supplier pages give them only at one temperature. The table below runs from −5 to 60 °C, which covers cold start through the warmest return water of a modern direct-to-chip loop.
| T °C | T °F | Density kg/m³ | Specific heat kJ/(kg·K) | Thermal cond. W/(m·K) | Viscosity mPa·s (cP) | Kinematic mm²/s (cSt) | Prandtl | ρ·cp kJ/(m³·K) |
|---|---|---|---|---|---|---|---|---|
| −5 | 23 | 1,032.8 | 3.851 | 0.436 | 6.84 | 6.63 | 60.5 | 3,977 |
| 0 | 32 | 1,031.2 | 3.864 | 0.443 | 5.42 | 5.25 | 47.3 | 3,984 |
| 5 | 41 | 1,029.6 | 3.876 | 0.450 | 4.36 | 4.23 | 37.6 | 3,991 |
| 10 | 50 | 1,027.8 | 3.888 | 0.456 | 3.56 | 3.46 | 30.3 | 3,996 |
| 15 | 59 | 1,025.9 | 3.901 | 0.462 | 2.94 | 2.87 | 24.8 | 4,002 |
| 20 | 68 | 1,023.9 | 3.913 | 0.468 | 2.47 | 2.41 | 20.6 | 4,006 |
| 25 | 77 | 1,021.7 | 3.925 | 0.473 | 2.09 | 2.05 | 17.4 | 4,010 |
| 30 | 86 | 1,019.4 | 3.938 | 0.478 | 1.80 | 1.76 | 14.8 | 4,014 |
| 35 | 95 | 1,017.0 | 3.950 | 0.483 | 1.56 | 1.53 | 12.8 | 4,017 |
| 40 | 104 | 1,014.5 | 3.962 | 0.487 | 1.37 | 1.35 | 11.1 | 4,020 |
| 45 | 113 | 1,011.8 | 3.975 | 0.491 | 1.21 | 1.20 | 9.8 | 4,021 |
| 50 | 122 | 1,009.0 | 3.987 | 0.495 | 1.08 | 1.07 | 8.7 | 4,023 |
| 55 | 131 | 1,006.1 | 3.999 | 0.498 | 0.97 | 0.97 | 7.8 | 4,024 |
| 60 | 140 | 1,003.0 | 4.012 | 0.501 | 0.88 | 0.88 | 7.0 | 4,024 |
Method. 25 % propylene glycol by mass in water at 3 bar, computed with the open-source CoolProp library (version 8.0.0), incompressible model APG, a fit to ASHRAE Handbook data. Cross-checked against CoolProp’s independent Melinder (2010) model: from 0 to 60 °C the two agree within 0.6 % on density, 0.3 % on specific heat and 2 % on thermal conductivity and viscosity. 25 % by volume is about 25.7 % by mass, a difference smaller than the spread between the two models. These are uninhibited-glycol correlation values: a formulated product differs slightly, and the purchased fluid’s supplier data sheet governs a design. Unit conversions: kg/m³ × 0.06243 = lb/ft³; kJ/(kg·K) × 0.2388 = Btu/(lb·°F); W/(m·K) × 0.5778 = Btu/(h·ft·°F); 1 mPa·s = 1 cP. Download the table as CSV.
PG25 vs Water: What the Glycol Costs, by Temperature
Hold the heat load, the temperature difference and the pipe diameter constant and swap water for PG25. The table gives the ratio PG25 / water from the property table above and the water properties at the same temperature (turbulent pipe flow, Blasius friction, Dittus–Boelter convection):
| Mean T °C | Flow | Kinematic viscosity | Pipe pressure drop | Pump power | In-tube heat transfer coeff. |
|---|---|---|---|---|---|
| 10 | ×1.049 | ×2.65 | ×1.43 | ×1.50 | ×0.60 |
| 20 | ×1.042 | ×2.40 | ×1.37 | ×1.43 | ×0.62 |
| 30 | ×1.037 | ×2.20 | ×1.33 | ×1.38 | ×0.64 |
| 40 | ×1.032 | ×2.05 | ×1.29 | ×1.33 | ×0.65 |
| 50 | ×1.027 | ×1.94 | ×1.26 | ×1.30 | ×0.66 |
Three things follow. The flow penalty is the smallest of the four effects — 3 to 5 % — while pump power rises 30 to 50 % and the in-tube heat-transfer coefficient falls by a third or more. Every penalty grows as the fluid gets colder, so a loop run at low supply temperature, or started cold, pays the most. And the heat-transfer loss, not the flow, is what reduces a CDU’s capability.
The published reference design states these ratios at 40 °C as flow ×1.045, pressure drop ×1.264, pump power ×1.321 and heat transfer ×0.69 [MODELED], derived in PG25 is not water plus 4.5 % volume. Those figures rest on the design’s assumed property set (density 1,012 kg/m³, specific heat 3.921 kJ/(kg·K), kinematic viscosity about 1.73× water). The ASHRAE-based correlation above puts viscosity at about 2.05× water at 40 °C, which gives a slightly smaller flow penalty (×1.032), slightly larger hydraulic penalties (×1.29, ×1.33) and a larger heat-transfer loss (×0.65). The conclusion is unchanged and somewhat stronger; the spread between two reasonable property sets is itself the case for designing on the purchased fluid’s own data.
PG25 Flow Rate per kW Calculator
Flow needed to carry a heat load at a given loop temperature rise, from the volumetric heat capacity in the table (Q = ρ·cp·V·ΔT). At a 10 K rise PG25 needs about 1.49 L/min per kW, against 1.45 for water.
Heat balance only. Real CDU and cold-plate flow targets come from the equipment vendor and include allowance for maldistribution; the default 136 kW is one rack of the published reference design.
OCP PG25 Guidelines (Revision 2.0, 2026): The Numbers That Matter
The Open Compute Project’s PG25 guideline was fully revised in September 2026 (95 pages, edited by Dow with contributors from fluid, filtration and lubricant suppliers; licensed CC BY-SA 4.0). It is the closest thing the industry has to a common PG25 specification. Its main limits, with the page they are on:
| Item | New fluid | In service | Page |
|---|---|---|---|
| Glycol, vol % | 24.5–27.5 | 24–29 (below 24: add supplier concentrate; above 29: dilute with qualified water) | 14, 67 |
| Freeze point | 9 to 14 °F (−13 to −10 °C) | 9 to 15 °F (−13 to −9 °C) | 15, 67 |
| pH | 8.0–10.5 (OAT: 7.0–10.5) | 8.0–10.5 (OAT/hybrid: 6.5–9.5) | 14, 68 |
| Reserve alkalinity (conventional inhibitors) | >6 mL | >4 mL | 14, 68 |
| Chloride / sulfate | <5 / <10 ppm | <25 / <25 ppm | 14, 69 |
| Copper, iron | — | <3 ppm each; above 5 ppm, test more often and consult the supplier | 69 |
| Flush and dilution water | Conductivity <25 µS/cm; dilution water chloride and sulfate <10 ppm | 55, 94 | |
| Filtration | Sidestream filtration of 5–15 % of flow strongly recommended above 250 gal; fill through 5–10 µm absolute | 26, 59 | |
| Laboratory analysis | Every loop at least annually, more often for higher-risk loops; baseline sample soon after start-up | 60–61 | |
| Metals qualification | Modified ASTM D8040: 336 h at 88 °C with aeration; copper and brass ≤0.2 mpy, 304L/316L stainless ≤0.1 mpy | 41–43 | |
Summarised from the OCP document; check the current revision and the fluid supplier’s own limits before writing a specification. OCP leaves density, viscosity, specific heat and thermal conductivity to suppliers, which is why the property table above is on this page. The full commissioning and maintenance sequence — flushing, fill, start-up, the sampling plan by risk level and the in-use actions — is in the PG25 loop commissioning and fluid-care checklist (4-page PDF, free, CC BY-SA 4.0).
Is PG25 Electrically Conductive?
Yes. PG25 is a water-based coolant, not a dielectric fluid. The inhibitor package carries ions, and OCP’s example in-line monitoring range is 1,000 to 10,000 µS/cm (page 82) — compare the less than 25 µS/cm it requires of flush and dilution water. Some suppliers formulate low-conductivity grades, but no PG25 is safe on energised electronics. The published design therefore handles leaks by isolation — valve sectioning and a bounded response — see 96 isolation valves and the auto-close trade-off. Conductivity is still worth trending: OCP suggests acting on a change of more than 20 % from baseline, because a drift signals contamination or inhibitor depletion.
The Capacity Derate: a Water-Rated 1.5 MW CDU Is 1.20–1.28 MW on PG25
Where a cooling distribution unit’s nameplate was calibrated on water, charging the loop with PG25 derates the real capability by a factor of about 0.80–0.85 [MODELED] — wide enough to change the unit count of a hall. The reference design carries the bottom of the band, 1.2 MW on a 1.5 MW water-basis nameplate, as the working derate, and registers the calibration fluid of the actual product as an item to close before any request for quotation. The reasoning, and the four conditions a capacity rating needs (Q = U·A·LMTD), are in the derate analysis. The larger heat-transfer loss given by the ASHRAE-based correlation above argues for staying at the bottom of that band.
Design Rules the Properties Impose
Pump and pipe sizing start from PG25 properties at the coldest expected operating temperature, never from water figures with a flow margin — the penalty lands in pressure drop and pump power, not mainly in flow. Capacity statements are only comparable with their fluid named. The purchased fluid’s supplier property table replaces the generic correlations used here (a CONFIRM item in the published design). The loop is closed: the design’s one-time first fill is about 30 tonnes of premixed, supplier-delivered fluid, which is not consumed in normal duty. Topping up with plain water dilutes the glycol and the inhibitors together, which is why OCP ties any adjustment to the supplier’s own concentrate and to qualified water.
The drawing set
Four books, 408 pages, free PDF, no account required, SHA-256 checksum for every file: Electrical, Public Edition P3 (108 pages) · Structural, Public Edition P2 (187 pages) · Network, Public Edition P2 (75 pages) · Liquid cooling, Public Edition P1 (38 pages). Checksums, release history and the smaller files (checklists, code, sample packs): downloads page. Design Development — Public Edition: for study; not issued for construction; not sealed. K&K Data Service Inc., Houston, publishes these sheets; the GB300-class project they describe is designed and not built. Field work, and what to send for a price, is on the Field work page.
Common Questions
What is PG25 coolant?
An inhibited mixture of about 25% propylene glycol by volume and 75% water plus corrosion inhibitors, used in the secondary loop (CDU to cold plates) of direct-to-chip liquid cooling. OCP specifies 24.5–27.5 vol% glycol for new fluid and 24–29% in service.
What is the density of PG25?
About 1,024 kg/m³ at 20 °C and 1,015 kg/m³ at 40 °C (generic ASHRAE-based correlation, 25% propylene glycol by mass). The table on this page gives density, specific heat, thermal conductivity and viscosity from −5 to 60 °C; a supplier data sheet governs design.
What is the specific heat of PG25?
About 3.91 kJ/(kg·K) at 20 °C and 3.96 kJ/(kg·K) at 40 °C, roughly 94–95% of water. Per unit volume the gap is smaller: 4,006 vs 4,176 kJ/(m³·K) at 20 °C, so PG25 needs only 3–5% more flow than water for the same heat and temperature rise.
What is the viscosity of PG25?
About 2.47 mPa·s (cP) at 20 °C, 1.37 at 40 °C and 5.42 at 0 °C — roughly two to two and a half times water across the usual operating range. Viscosity is what drives the extra pressure drop, pump power and lost heat transfer.
What is the freezing point of PG25?
OCP gives 9 to 14 °F (−13 to −10 °C) for new PG25, measured by ASTM D3321, and 9 to 15 °F (−13 to −9 °C) for in-service fluid at 24–29% glycol. Correlations for 25% glycol by mass give about −10 °C. Freeze protection depends on keeping the glycol concentration in range.
Is PG25 electrically conductive?
Yes. It is a water-based coolant, not a dielectric; OCP's example in-line monitoring range is 1,000–10,000 µS/cm. Leak response must assume a conductive fluid, which is why the published design relies on isolation valves and bounded response.
How does PG25 compare with water?
At 40 °C, for the same heat, temperature rise and pipe: about 3% more flow, 29% more pressure drop, 33% more pump power and 35% lower in-tube heat-transfer coefficient (ASHRAE-based correlation). The reference design's own basis gives ×1.045, ×1.264, ×1.321 and ×0.69. The penalties grow as the fluid gets colder.
How often should PG25 be tested?
OCP asks for laboratory analysis of every loop at least once a year, more often for higher-risk loops, plus a baseline sample shortly after start-up. Typical checks: glycol %, pH, reserve alkalinity, appearance, copper and iron, chloride and sulfate.
Does a PG25 loop consume coolant?
Not in normal duty: the loop is closed. The published design has a one-time first fill of about 30 tonnes of premixed fluid, no evaporative consumption, and makeup only after service events.