The Numbers Behind a GB300-Class Data Center, With Sources
Writers and engineers keep needing the same numbers — and the vendor sources are gated. This page collects the working figures of our published reference design, each with its maturity label, a one-line explanation and a deep-linkable source. Cite them freely with attribution.

Power
136 kW per rack, A/B dual feed
IT design basis of the electrical reference design: 136 kW per rack with 50/50 normal sharing across dual inputs. [design basis] Source · #
952 kW normal / 1428 kW single-path outage
Per-path IT duty on a six-path, 42-rack zone: what one power path carries normally, and what it must carry when its partner path is out. [design basis] Source · #
2 MW UPS design duty per path
Each radial path carries one UPS block at 2 MW design duty; a 2 x 1200 kVA/kW frame is the stated candidate. Independent UPS outputs are kept un-paralleled. [design basis] Source · #
A 42-rack GPU zone is 5,712 kW
42 racks × 136 kW = 5,712 kW per zone, before cooling and losses. [arithmetic on the design basis] Source · #
2500 kVA, 12.47 kV to 480Y/277 V, one transformer per path
Critical-power transformer calculation basis on every radial path; each secondary feeds exactly one LV breaker, one ATS and one UPS. [design basis] Source · #
16 x 1 MW generator plant in 4 sections with 3 sync-check couplers
Generator plant study basis serving 13 UPS feeders; first machine closes to a verified dead bus, everything after needs a synchronism-check permissive. [study basis] Source · #
Half a point of UPS efficiency moves 65 kW against an 85 kW utility margin
Why partial-load UPS efficiency is a procurement number, not a datasheet footnote: at this design's scale, 0.5% of efficiency is 65 kW of continuous load against a thin utility margin. [arithmetic on the design basis] Source · #
Cooling
A water-rated 1.5 MW CDU delivers about 1.20–1.28 MW on PG25
Nameplate CDU ratings are stated on water; on 25% propylene glycol the modeled delivered capacity drops 15–20%. [modeled] Source · #
155 kW sustained per rack, 95% heat rejection to liquid
Sizing basis of the liquid-cooling set (V8.5): 883.50 kW per 6-rack unit, 2,650.50 kW per 18-rack group, 13.2525 MW liquid load across 90 racks. A deliberately heavier basis than the electrical set's 136 kW IT figure — each discipline states its own. [design assumption] Source · #
A 90-second source transfer at 330 m³/h needs 8.25 m³ of deliverable cold liquid
Why buffer tanks are sized the way they are: the stated transfer-event requirement works out to 8.25 m³ of cold volume; a 15 m³ nominal buffer per ring carries it with stratification margin. [design requirement] Source · #
37/40 °C normal supply; 41/44 °C high-temperature mode; 45 °C hard limit
Primary/secondary coolant temperature ladder of the liquid-cooling reference design; wet cooling is an intended operating mode above 35 °C outdoor dry bulb, not an emergency mode. [design requirement] Source · #
PG25 vs water at 40 °C: flow ×1.045, pressure drop ×1.264, pump power ×1.321, heat transfer ×0.69
The four property ratios of 25% propylene glycol against treated water on the design's assumed property set — the familiar 4.5% flow figure is the smallest of the four effects; an ASHRAE-based correlation gives ×1.03, ×1.29, ×1.33 and ×0.65. [modeled] Source · #
Structure
Site and civil
60 inches of conduit cover; ~1788 mm excavation
Adopted medium-voltage buried-crossing basis under the shared heavy-vehicle road: 114.3 mm conduit OD plus 150 mm bed gives roughly 1788 mm of excavation — deep enough that worker entry needs an OSHA 1926.652 protective system. [design basis] Source · #
Water
No evaporative water consumption in normal operation, by design
Dry coolers carry normal duty and the PG25 loop is closed; evaporative wet-assist exists only as a bounded exception mode for sustained heat or dry-cooler outage. [design basis] Source · #
First fill ≈30 t premixed coolant (≈7,700 US gal), one-time, supplier-delivered
A one-time system inventory with a stated range of ±30% — not municipal water and not a recurring draw. [design basis] Source · #
Ten-year emergency-water planning allowance ≈150 t ≈ 39,600 US gallons
One hundred hours at the 1.5 t/h make-up allowance — about 11.4 minutes of the reported 5-million-gallon-per-day ceiling for a large facility; a site whose counted spray hours exceed the budget scales it in proportion. [planning allowance] Source · #
Scale of the published record
408 pages of drawings + 108 analysis articles, free
Electrical 108 (Public Edition P3), structural 187 (Public Edition P2), network 75 (Public Edition P2), liquid cooling 38 pages — plus 108 Lab articles. Every file carries a published SHA-256; every Lab number carries a maturity label. [record] Source · #
How to cite these numbers
Every figure on this page is published in the K&K reference drawing set or the Data Center Lab, with its maturity stated in the bracket: a design basis is what the drawings are engineered around, a modeled figure is calculated analysis, a requirement is a stated performance target — none of them are field measurements. Cite freely with attribution: link either this page (each number has a # anchor) or the linked source. These are reference-design figures for study and evaluation; verify against your own equipment data before use.
Reusing the drawings and figures
The drawing images published on this site (one-line diagrams, equipment plans, sheet renders) may be reused in articles, presentations and teaching material with visible attribution to K&K Data Service Inc. and a link to kkdatasvc.com. The PDF sets carry their own attribution terms inside each document. For other uses, write to inquiry@kkdatasvc.com.
The drawing set
Four books, 408 pages, free PDF, no account required, SHA-256 checksum for every file: Electrical, Public Edition P3 (108 pages) · Structural, Public Edition P2 (187 pages) · Network, Public Edition P2 (75 pages) · Liquid cooling, Public Edition P1 (38 pages). Checksums, release history and the smaller files (checklists, code, sample packs): downloads page. Design Development — Public Edition: for study; not issued for construction; not sealed. K&K Data Service Inc., Houston, publishes these sheets; the GB300-class project they describe is designed and not built. Field work, and what to send for a price, is on the Field work page.
Common Questions
How much power does a GB300-class rack actually draw?
Published rack-scale figures are on the order of 135–150 kW, fully liquid cooled. The reference design on this site carries a 136 kW-per-rack electrical IT basis and a deliberately heavier 155 kW sustained basis in its liquid-cooling sizing — both stated with their assumptions.
Are these numbers measured from a real facility?
No, and the page says so on every figure: they are design bases, modeled analysis and stated requirements from a published reference design (Design Development — Public Edition), not field measurements. That honesty is the point — each figure links its source so you can judge it.
Can I use these numbers in my own article or deck?
Yes — cite the page or the linked source with attribution. Each figure has a # anchor for deep linking. Drawing images may be embedded with visible attribution and a link.
Questions about any sheet or parameter: inquiry@kkdatasvc.com or the contact page.